ZR 8500 Nitrogen Control System
Model ZR8500
Nitrogen Control System
The Nitrosave control system combined with a state of the art trace and percent oxygen measurement technology offers cost of ownership with pay back times in Nitrogen savings within a few years.
Specifications
- Range: 0.01ppm - 100% O2 Autoranging
- Sensor Type Stabilised zirconia sensor
- Ranges 0.01ppm - 100% O2 Autoranging
- Accuracy Dependent on measurement method
- Communications USB and RS485
- Alarms 2 programmable changeover contacts, rated 240V 3A
- 1 fault alarm, changeover contact, rated 240V 3A
- Analog Outputs 2 scaleable 4-20mA or 0-20mA all isolated.
- 1 for control valve.
- Power Supply: 115 / 230 VAC, 50 / 60 Hz, 24VDC version option.
- Enclosure: Bench/Panel Mount
- Dimension: 7.48H x 9.33W x 16.14D (inches) weight 17.4 lbs
- Unsuitable Gases H2S, Ammonia, Corrosive gases, Hydrocarbons, Combustibles, Hydrogen, NO2, Carbon Monoxide, Halogenated Hydrocarbons, Sulphur containing compounds, Halogens, Lead containing compounds.
Note: Optional version for use with gases containing low ppm levels of hydrocarbons, combustibles, hydrogen and carbon monoxide for high purity analysis.
Features and benefits
- Save on nitrogen usage and rework c0osts.
- Improve process control and product quality.
- Automatically detects a halt in production and reduces nitrogen flow for even greater savings.
- Extremely fast response time even after high oxygen exursions means quicker process optimization.
- Nitrosave Viewer PC software makes set up quick and easy.
- USB and RS485 communications output for data logging can document the whole process.
- Small footprint allows OEM manufacturers to install inside their machines.
Applications
Soldering ovens
UV Curing Systems
Food Packaging machines
Conforms to European Directives:
Electromagnetic Compatibility Directive 89/336/EEC Low Voltage Directive 73/23/EEC
Unmatched Performance
Nitrosave consists of the oxygen monitor/control unit and a proportional or other control valve which is fitted into the nitrogen supply line to the machine.
Nitrosave monitors the residual oxygen in the system under control using our latest cell technology. The oxygen measurement is then used together with a fuzzy logic control algorithm and user-defined setpoints for desired oxygen level, to automatically control the
opening of the valve, which regulates the flow of nitrogen into the machine.
This ensures enough nitrogen to comfortably maintain the desired oxygen level is fed into the machine but eliminates the waste seen with fixed-flow nitrogen systems.
Installation of the Nitrosave is very simple and it can be retrofitted to almost all types of machines.